Over Excitation Limiter Model: OEL4C
Following checks and corrections are applied during Validation and AutoCorrection.
-
Kp and Ki: Kp can't be 0 if Ki = 0, if true then Kp changed to 40.
Mult represents the user-specified value Minimum time constant size as multiple of time step option on the Validation page of the Transient Stability Dialog
TimeStep represents the integration time step being used as described on TimeStep
Model Equations and/or Block Diagrams
Parameters:
| Qref | Reactive power limit, per unit on machine base; the default of zero means to use the power flow Qmax |
| TDelay | Time delay to begin enforcement, seconds |
| Kp | PI proportional gain |
| Ki | PI integral gain |
| Vmin | Maximum value to change voltage reference, must be always <= 0 |